3 functions in one unit, insulation test with 4 voltage ranges, continuity test, AC voltage measurement |
• |
200mA measuring current on continuity testing |
• |
Comparator function with PASS / FAIL and buzzer |
• |
0Ω adjustment at continuity measuring range |
• |
Memory function up to 99 data |
• |
Backlight LCD provides easy reading in dark locations |
• |
Safety lock system prevents an erroneous operation on 500 and 1000 Volt ranges |
• |
Safety standard IEC 61010-01 CAT III 600V |
|

  |
|
 |
3021 |
|
|
|
Insulation resistance |
Test voltage |
125V |
250V |
500V |
1000V |
Measuring range (Auto range) |
4.000/40.00/ 200.0MΩ |
4.000/40.00/400.0/2000MΩ |
First Effective Measuring range |
0.1 - 20MΩ |
0.1 - 40MΩ |
0.1 - 200MΩ |
0.1 - 1000MΩ |
Mid-scale value |
5MΩ |
50MΩ |
Accuracy |
|±2%rdg±6dgt |
Second effective measuring range lower |
0 - 0.099MΩ |
Second effective measuring range upper |
20.01 - 200.0MΩ |
40.01 - 2000MΩ |
200.1 - 2000MΩ |
1001 - 2000MΩ |
Accuracy |
|±5%rdg±6dgt |
Rated current |
DC 1 - 1.2mA |
Output short circuit current |
1.5mA max |
Ω/Continuity |
Auto range |
40.00/400.0Ω |
Accuracy |
|±2%rdg±8dgt |
Output Voltage on open circuit |
5V±20% |
Output short circuit current |
DC 220±20mA |
Fuse |
Quick acting ceramic fuse 0.5A/600V (Ø6.35×32mm) |
AC Voltage |
Range |
AC 20 - 600V (50/60Hz) DC -20 - -600V/+20 - +600V |
Accuracy |
|±3%rdg±6dgt |
General |
Applicable standards |
IEC 61010-1 CAT III 600V, IEC 61557-1,2,4, IEC 61326-1 (EMC), IEC 60529 (IP40) |
Dimensions / Weight |
105(L) × 158(W) × 70(D)mm / 600g approx. |
Power source |
R6 × 6 or LR6 × 6 |
Accessories |
7150A (Remote control switch set), 9121 (Shoulder strap), R6 (AA) × 6, Instruction Manual |
Optional |
7115 (Extension Probe), 8016 (Hook type prod), 8923 (Fuse [0.5A/600V]), 9089 (Carrying Case) |
|
|

|
3022 |
|
|
|
Insulation resistance |
Test voltage |
50V |
100V |
250V |
500V |
Measuring range (Auto range) |
4.000/40.00/200.0MΩ |
4.000/40.00/400.0/2000MΩ |
First Effective Measuring range |
0.1 - 20MΩ |
0.1 - 40MΩ |
0.1 - 200MΩ |
Mid-scale value |
5MΩ |
50MΩ |
Accuracy |
|±2%rdg±6dgt |
Second effective measuring range lower |
0 - 0.099MΩ |
Second effective measuring range upper |
20.01 - 200.0MΩ |
40.01 - 2000MΩ |
200.1 - 2000MΩ |
Accuracy |
|±5%rdg±6dgt |
Rated current |
DC 1 - 1.2mA |
Output short circuit current |
1.5mA max |
Ω/Continuity |
Auto range |
40.00/400.0Ω |
Accuracy |
|±2%rdg±8dgt |
Output Voltage on open circuit |
5V±20% |
Output short circuit current |
DC 220±20mA |
Fuse |
Quick acting ceramic fuse 0.5A/600V (Ø6.35×32mm) |
AC Voltage |
Range |
AC 20 - 600V (50/60Hz) DC -20 - -600V/+20 - +600V |
Accuracy |
|±3%rdg±6dgt |
General |
Applicable standards |
IEC 61010-1 CAT III 600V, IEC 61557-1,2,4, IEC 61326-1 (EMC), IEC 60529 (IP40) |
Dimensions / Weight |
105(L) × 158(W) × 70(D)mm / 600g approx. |
Power source |
R6 × 6 or LR6 × 6 |
Accessories |
7150A (Remote control switch set), 9121 (Shoulder strap), R6 (AA) × 6, Instruction Manual |
Optional |
7115 (Extension Probe), 8016 (Hook type prod), 8923 (Fuse [0.5A/600V]), 9089 (Carrying Case) |
|
|

|
3023 |
|
|
|
Insulation resistance |
Test voltage |
100V |
250V |
500V |
1000V |
Measuring range (Auto range) |
4.000/40.00/ 200.0MΩ |
4.000/40.00/400.0/2000MΩ |
First Effective Measuring range |
0.1 - 20MΩ |
0.1 - 40MΩ |
0.1 - 200MΩ |
0.1 - 1000MΩ |
Mid-scale value |
5MΩ |
50MΩ |
Accuracy |
|±2%rdg±6dgt |
Second effective measuring range lower |
0 - 0.099MΩ |
Second effective measuring range upper |
20.01 - 200.0MΩ |
40.01 - 2000MΩ |
200.1 - 2000MΩ |
1001 - 2000MΩ |
Accuracy |
|±5%rdg±6dgt |
Rated current |
DC 1 - 1.2mA |
Output short circuit current |
1.5mA max |
Ω/Continuity |
Auto range |
40.00/400.0Ω |
Accuracy |
|±2%rdg±8dgt |
Output Voltage on open circuit |
5V±20% |
Output short circuit current |
DC 220±20mA |
Fuse |
Quick acting ceramic fuse 0.5A/600V (Ø6.35×32mm) |
AC Voltage |
Range |
AC 20 - 600V (50/60Hz) DC -20 - -600V/+20 - +600V |
Accuracy |
|±3%rdg±6dgt |
General |
Applicable standards |
IEC 61010-1 CAT III 600V, IEC 61557-1,2,4, IEC 61326-1 (EMC), IEC 60529 (IP40) |
Dimensions / Weight |
105(L) × 158(W) × 70(D)mm / 600g approx. |
Power source |
R6 × 6 or LR6 × 6 |
Accessories |
7150A (Remote control switch set), 9121 (Shoulder strap), R6 (AA) × 6, Instruction Manual |
Optional |
7115 (Extension Probe), 8016 (Hook type prod), 8923 (Fuse [0.5A/600V]), 9089 (Carrying Case) |
|
|
|
|
|